NFPA issues safety alert regarding antifreeze in residential sprinklers


         Subscribe in NewsGator Online   Subscribe in Bloglines

QUINCY, MASS. — The National Fire Protection Association (NFPA) recently issued a safety alert recommending that residential fire sprinkler systems containing antifreeze should be drained and the antifreeze replaced with water.

The alert follows a research study and an initial set of fire tests conducted after a fire incident raised concerns about antifreeze solutions in residential sprinkler systems. The incident involved a grease fire in a kitchen where a sprinkler with a high concentration of antifreeze deployed. The fire resulted in a single fatality and serious injury to another person.

“Fire sprinklers are one of the most effective ways to save lives and property from fire,” said James M. Shannon, president of NFPA. “Until we can provide further information based on additional research that is currently underway, we are urging the public to continue the use of sprinklers but to follow our interim safety guidelines by removing antifreeze if it is in their sprinkler systems."

Shannon said based on testing conducted, 70%/30% glycerin and 60%/40% propylene glycol antifreeze may provide an unacceptable risk of harm to occupants in certain types of fire scenarios, in particular kitchen grease fires.

There were successful tests where kitchen grease fires were extinguished or contained with a 50%/50% glycerin solution but it was felt there should be additional testing to more fully understand if there is a risk associated with 50%/50% glycerin solution.

NFPA offers the following interim guidance on residential sprinklers: fire sprinklers are extremely effective fire protection devices, significantly reducing deaths, injuries and property loss from fire, and these systems should not be disconnected.

Until the results of further testing on antifreeze are available, NFPA recommends the following:

-If you have, or are responsible for, a residential occupancy with a fire sprinkler system, contact a sprinkler contractor to check and see if there is antifreeze in the system.

-If there is antifreeze in the system, as an interim measure, drain the system and replace it with water only. Problems associated with freezing of sprinkler pipes can be mitigated by alternative measures such as insulation. NFPA hopes to provide further guidance based on additional testing before the winter freezing months.

-If you are putting in a new residential sprinkler system, design and install a system that does not require antifreeze.

“We are providing this safety alert as interim guidance based on the information we have right now,” said Shannon. “As soon as more information is available, we will update the public.”

Click here for additional information about the safety alert regarding antifreeze in residential sprinklers.

Want to use this article? Click here for options!
© 2012 Penton Media Inc.


Acceptable Use Policy
blog comments powered by Disqus

Social Media

Follow us on

Become a fan on

Opinion Poll

Reader Comments

Powered by Disqus

Best of 2010!


Here are Contractormag's top articles of 2010.
Click here to see if your favorites made the list!

  • February 2012 cover
  • January 2012 cover
  • December 2011 cover
  • November 2011 cover
  • October 2011 cover
  • September 2011 cover
  • August 2011 cover

Browse Back Issues